Exergy analysis of R1234ze(Z) as high temperature heat pump working fluid with multi-stage compression

Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, Shanghai 200240, China

录用日期: 2017-11-14 发布日期: 2017-12-14

下一篇 上一篇

摘要

In this paper, the simulation approach and exergy analysis of multi-stage compression high temperature heat pump (HTHP) systems with R1234ze(Z) working fluid are conducted. Both the single-stage and multi-stage compression cycles are analyzed to compare the system performance with 120°C pressurized hot water supply based upon waste heat recovery. The exergy destruction ratios of each component for different stage compression systems are compared. The results show that the exergy loss ratios of the compressor are bigger than that of the evaporator and the condenser for the single-stage compression system. The multi-stage compression system has better energy and exergy efficiencies with the increase of compression stage number. Compared with the single-stage compression system, the coefficient of performance (COP) improvements of the two-stage and three-stage compression system are 9.1% and 14.6%, respectively. When the waste heat source temperature is 60°C, the exergy efficiencies increase about 6.9% and 11.8% for the two-stage and three-stage compression system respectively.