Comprehensive performance analysis and optimization of 1,3-dimethylimidazolylium dimethylphosphate-water binary mixture for a single effect absorption refrigeration system

Collage of Engineering, Qatar University, Doha 2713, Qatar

录用日期: 2021-01-25 发布日期: 2021-01-25

下一篇 上一篇

摘要

The energy and exergy analyses of the absorption refrigeration system (ARS) using H O-[mmim][DMP] mixture were investigated for a wide range of temperature. The equilibrium Dühring ( - - ) and enthalpy ( - - ) of mixture were assessed using the excess Gibbs free non-random two liquid (NRTL) model for a temperature range of 20°C to 140°C and from 0.1 to 0.9. The performance validation of the ARS cycle showed a better coefficient of performance (COP) of 0.834 for H O-[mmim][DMP] in comparison to NH -H O, H O-LiBr, H O-[emim][DMP], and H O-[emim][BF4]. Further, ARS performances with various operating temperatures of the absorber ( ), condenser ( ), generator ( ), and evaporator ( ) were simulated and optimized for a maximum COP and exergetic COP (ECOP). The effects of from 50°C to 150°C and and from 30°C to 50°C on COP and ECOP, the , , and circulation ratio (CR) of the ARS were evaluated and optimized for from 5°C to 15°C. The optimization revealed that needed to achieve a maximum COP which was more than that for a maximum ECOP. Therefore, this investigation provides criteria to select low grade heat source temperature. Most of the series flow of the cases of cooling water from the condenser to the absorber was found to be better than the absorber to the condenser.