Journal Home Online First Current Issue Archive For Authors Journal Information 中文版

Strategic Study of CAE >> 2005, Volume 7, Issue 9

Experimental Study on Temperature Distribution and Response Behaviors of Steel Element under Corner Fire Conditions

State Key Laboratory of Fire Science , USTC, Hefei 230026, China

Funding project:国家自然科学基金重大国际合作研究资助项目(50320120156),国家重点基础研究发展规划资助项目(2001CB409603) Received: 2004-09-02 Available online: 2005-09-20

Next Previous

Abstract

By using ISO9705 Room/Corner Fire Test Rig, thin steel tubes were tested. The response behaviors of steel element under thermal-mechanical coupling effect in a simulated corner fire were studied. In the experiment, the heat release rate and temperature field of the fire, temperature and deflection of the steel element and the temperature of the gas close to steel surface were measured. Effects of the temperature elevation and distribution of the steel element under corner fire conditions along with the fire growth on the deflection were analyzed. Results show that there exists significant temperature difference along the longitude of the steel and an unsymmetrical deflection variation. These indicate that assumptions of the uniform temperature distribution along the longitude direction in previous studies were improper. Under this non-uniform temperature distribution, failure resulted from the local yield of the higher temperature zone of the element is more inclined to occur. Indeed, this non-uniform temperature distribution caused by the corner fire is more dangerous to the fire safety of steel elements than the even case under same fire size.

Figures

图1

图2

图3

图4

图5

图6

图7

图8

References

[ 1 ] BS5950 Structural Use of Steelwork in building.Part1:Code of Practice for Design in Simple andContinuous Construction, Hot Rolled Sections[S].London:British Standards Institution, 1990

[ 2 ] Eurocode 3 Design of Steel Structures, Part 1.2:General Rules, Structural Fire Design[S].London:British Standards Institution, 2000

[ 3 ] 李国强, 贺军利, 蒋首超.钢柱的抗火试验与验算[J].建筑结构, 2000, 30 (9) :12~15 link1

[ 4 ] Sanad A M, Lamont S, Usmani A S, Rotter J M.Structural behaviour in fire compartment underdifferent heating regimes-Part 1: (slab thermalgradients) [J].Fire Safety Journal, 2000, 35 (4) :99~116

[ 5 ] Sanad A M, Lamont S, Usmani A S, Rotter J M.Structural behaviour in fire compartment underdifferent heating regimes-Part 2: (slab meantemperatures) [J], Fire Safety Journal, 2000, 35 (4) :117~130

[ 6 ] 赵金城.高温下钢结构压弯构件的整体稳定性极限状[J].钢结构, 1998, 13 (42) :31~34 link1

[ 7 ] Usmani A S, Rotter J M, Lamont S, Sanad A M, Gillie M.Fundamental principles of structuralbehaviour under thermal effects[J].Fire SafetyJournal, 2001, 36 (8) :721~744

[ 8 ] Becker R.Effects of heat sinks on evolution oflongitudinal temperature distributions in steel structures[J].Fire Safety Journal, 2002, 37 (1) :1~20

[ 9 ] Becker R.Structural behavior of simple steel structureswith non-uniform longitudinal temperaturedistributions under fire conditions[J], Fire SafetyJournal, 2002, 37 (5) :495~515

[10] ISO-9705 Fire tests Full-scale Room Test for SurfaceProducts[S].Geneva:International StandardsOrganization (ISO) , 1993

[11] 杨昀, 张和平, 刘激扬.室内装饰材料的标准房间/墙角火实验研究进展[J].中国工程科学, 2003, 5 (4) :55~60 link1

[12] 杨昀, 张和平, 王蔚, 徐亮, 万玉田.典型建筑装饰材料热释放速率全尺寸火灾实验研究[J].火灾科学, 2003, 12 (4) :191~196 link1

[13] European Committee for Standardisation (CEN) DraftprEN 1991-1-2, Eurocode 1, Basis of Design andActions on Structures, Part 1.2:Actions onStructures-Actions on Structures Exposed to Fire[S].London:British Standards Institution, 2000

[14] Wang Y C.Steel and Composite Structures-Behaviourand Design for Fire Safety[M].London:Spon Press, 2002

[15] Kay T R, Kirby B R, Preston R R.Calculation of theheating rate of an unprotected steel member in astandard fire resistance test[J].Fire Safety Journal, 1996, 26 (4) :327~350