The pressure loss of the upper and lateral ventilation panels at different air velocities was obtained by means of experiments in this study. An experiment on ventilation panels was carried out at the Central South University model test platform in China, which has obtained China Metrology Accreditation (CMA) qualification (certificate number 2014002479K). More detailed information about the platform is provided in Refs. [
30] and [
31]. The air velocities were 1, 2, 3, 4, and 5 m·s
−1. The experimental model was constructed according to the actual size of the ventilation panel, as shown in Fig. 6(a). A Honeywell DC030NDC4 pressure sensor was selected for pressure measurement, as shown in Fig. 6(b). The sampling frequency of the sensors was 1 kHz in this set of tests, and the measurement accuracy was 0.01 Pa. For velocity measurement, a TSI9525 anemometer with a hot-wire wind-speed probe was adopted, with a measurement accuracy of 0.01 m·s
−1. Before each test, every sensor had to be recalibrated and calibrated. The error of the loading test was within 0.2%, which is considered to meet the test accuracy requirements. Each case was repeated five times, and the acceptability in terms of air velocity was examined. Tests that did not meet the required accuracy of ±0.2% of the target air velocity were discarded. The average of the data from the five tests was defined as the experimental results. Table 1 shows the experimental results for ventilation panel pressure loss. In this table,
v and Δ
p are the same variables as in Eq. (1), and “upper” and “lateral” represent the upper and lateral ventilation panels. Table 2 provides the fitting equations and fitting goodness of the ventilation panel pressure loss based on the experimental results. In this table,
R2 represents the fitting measure cofficients. Introducing the constants into the coefficients in Table 2 yields the porous media parameters 1/
α and
C2 of the ventilation panel, as shown in Table 3.