地下长通道补气口位置对火灾机械排烟效率的影响

胡隆华,霍然,李元洲,易亮,王浩波

中国工程科学 ›› 2005, Vol. 7 ›› Issue (5) : 90 -92.

PDF (3642KB)
中国工程科学 ›› 2005, Vol. 7 ›› Issue (5) : 90 -92.
研究报告

地下长通道补气口位置对火灾机械排烟效率的影响

作者信息 +

Effect of Position of Air Supply Opening on the Efficiency of Smoke Extraction in an Underground Long Channel

Author information +
文章历史 +
PDF (3729K)

摘要

在地下长通道内开展了针对一组相对位置不同的补气口—排烟口的排烟效果的全尺寸对比试验。结果表明,在地下长通道内设置的补气口—排烟口在针对发生火灾情况的优化组合上,应尽量遵循“远端补气、近端排烟”的原则。

Abstract

A set of full scale contrast tests, with different relative positions of air supply opening and smoke exhaust opening, were conducted in an 88 m long underground corridor to study the effect of position of air supply opening on the efficiency of smoke extraction in a long channel. Results showed that the rule for designing the relative positions of air supply openings and smoke exhaust openings or operating them in a long channel should be “Smoke exhaust near the fire with air supply far away from the fire”.

关键词

地下长通道 / 补气口 / 排烟口 / 机械排烟效率 / 火灾

Key words

air supply position / smoke extraction efficiency / underground long channel / full scale test / fire