《能源前沿(英文)》 >> 2008年 第2卷 第1期 doi: 10.1007/s11708-008-0010-9

Thermal-hydraulic performance of novel louvered fin using flat tube cross-flow heat exchanger

Institute of Refrigeration and Cryogenics, Shanghai Jiaotong University

发布日期: 2008-03-05

下一篇 上一篇

摘要

Experimental studies were conducted to investigate the air-side heat transfer and pressure drop characteristics of a novel louvered fins and flat tube heat exchangers. A series of tests were conducted for 9 heat exchangers with different fin space and fin length, at a constant tube-side water flow rate of 2.8 m/h. The air side thermal performance data were analyzed using the effectiveness-NTU method. Results were presented as plot of Colburn factor and friction factor against the Reynolds number in the range of 500–6500. The characteristics of the heat transfer and pressure drop of different fin space and fin length were analyzed and compared. In addition, the curves of the heat transfer coefficients vs. pumping power per unit heat transfer area were plotted. Finally, the area optimization factor was used to evaluate the thermal hydraulic performance of the louvered fins with differential geometries. The results showed that the and factors increase with the decrease of the fin space and fin length, and the fin space has more obvious effect on the thermal hydraulic characteristics of the novel louvered fins.