Influence of Thermal Flow Field of Cooling Tower on Recirculation Ratio of a Direct Air-Cooled System for a Power Plant

赵万里

中国工程科学 ›› 2008, Vol. 10 ›› Issue (4) : 64-70.

PDF(1082 KB)
PDF(1082 KB)
中国工程科学 ›› 2008, Vol. 10 ›› Issue (4) : 64-70.

Influence of Thermal Flow Field of Cooling Tower on Recirculation Ratio of a Direct Air-Cooled System for a Power Plant

  • 赵万里
作者信息 +

Influence of Thermal Flow Field of Cooling Tower on Recirculation Ratio of a Direct Air-Cooled System for a Power Plant

  • zhao wanli
Author information +
History +

摘要

In order to get thermal flow field of direct air-cooled system, the hot water was supplied to the direct air-cooled condenser. The PIV experiments were carried out to get thermal flow field of a direct air-cooled system under different conditions in low velocity wind tunnel, at the same time, the recirculation ratio at cooling tower was measured, so the relationship between flow field characteristic and recirculation ratio of cooling tower can be discussed, from the results we can see that: the flow field configuration fore-and-aft cooling tower has great effects on average recirculation ratio under cooling tower. The eddy formed fore-and-aft cooling tower is a key reason that recirculation produces. The eddy intensity relates to velocity magnitude and direction angle, the configuration of eddy lies on the geometry size of cooling tower. So changing the flow field configuration fore-and-aft cooling tower reasonably can decrease recirculation ratio under cooling tower, and heat dispel effect of ACC can also be improved.

Abstract

In order to get thermal flow field of direct air-cooled system, the hot water was supplied to the direct air-cooled condenser. The PIV experiments were carried out to get thermal flow field of a direct air-cooled system under different conditions in low velocity wind tunnel, at the same time, the recirculation ratio at cooling tower was measured, so the relationship between flow field characteristic and recirculation ratio of cooling tower can be discussed, from the results we can see that: the flow field configuration fore-and-aft cooling tower has great effects on average recirculation ratio under cooling tower. The eddy formed fore-and-aft cooling tower is a key reason that recirculation produces. The eddy intensity relates to velocity magnitude and direction angle, the configuration of eddy lies on the geometry size of cooling tower. So changing the flow field configuration fore-and-aft cooling tower reasonably can decrease recirculation ratio under cooling tower, and heat dispel effect of ACC can also be improved.

关键词

Power Plant / Direct Air-Cooled Condenser / Thermal Flow Field Characteristics / Recirculation Ratio / PIV Experiment

Keywords

Power Plant / Direct Air-Cooled Condenser / Thermal Flow Field Characteristics / Recirculation Ratio / PIV Experiment

引用本文

导出引用
赵万里. Influence of Thermal Flow Field of Cooling Tower on Recirculation Ratio of a Direct Air-Cooled System for a Power Plant. 中国工程科学. 2008, 10(4): 64-70