Reasonable Rated Voltage of High and Medium Power Adjustable-Speed Drives for Energy Saving

Ma Xiaoliang

Strategic Study of CAE ›› 2001, Vol. 3 ›› Issue (11) : 80-84.

PDF(2898 KB)
PDF(2898 KB)
Strategic Study of CAE ›› 2001, Vol. 3 ›› Issue (11) : 80-84.
Comprehensive Review

Reasonable Rated Voltage of High and Medium Power Adjustable-Speed Drives for Energy Saving

  • Ma Xiaoliang

Author information +
History +

Abstract

A large amount of energy will be saved if adjustable-speed drives are adopted by high and medium power pumps and fans. The power range of most of the drives is within 0.2~2 MW. The rated voltage of most of the motors in the power range is 10 kV because the power supply is 10 kV. The adjustable-speed scheme, a 10 kV motor is fed by a 10 kV inverter, is not reasonable because this kind of inverter consists of a lot of power electronic devices in series and its cost is high and reliability is poorer than lower voltage one. Owing to the existence of input transformer of the inverter, it is not necessary to ask for that the rated voltage of the motor and inverter is the same as power supply, i. e. a lower rated voltage can be used for the motor and inverter. The reasonable rated voltages of motors and inverters with different power grades are investigated and the by-pass methods when the rated voltages of the motors are different from power supply are discussed in this paper.

Keywords

high and medium power / adjustable-speed drives for energy saving / reasonable rated voltage / low voltage inverters / medium voltage inverters / by-pass

Cite this article

Download citation ▾
Ma Xiaoliang. Reasonable Rated Voltage of High and Medium Power Adjustable-Speed Drives for Energy Saving. Strategic Study of CAE, 2001, 3(11): 80‒84
AI Summary AI Mindmap
PDF(2898 KB)

Accesses

Citations

Detail

Sections
Recommended

/