Study of Suppressing PVC Fire with Water Mist Using a Cone Calorimeter

Huang Xin、 Liu Jianghong、 Zhang Yongfeng、 Qin Jun

Strategic Study of CAE ›› 2006, Vol. 8 ›› Issue (12) : 102-106.

PDF(2920 KB)
PDF(2920 KB)
Strategic Study of CAE ›› 2006, Vol. 8 ›› Issue (12) : 102-106.
Research Report

Study of Suppressing PVC Fire with Water Mist Using a Cone Calorimeter

  • Huang Xin、 Liu Jianghong、 Zhang Yongfeng、 Qin Jun

Author information +
History +

Abstract

In this paper, the action of water mist on PVC fires in a cone calorimeter under different external radiant heat fluxes was studied and the reignition of the PVC fires was analyzed. Water mist was generated by a single pressure nozzle. Physical characteristics of the water mist were measured by LDV/APV system. The heat release rate, oxygen, carbon dioxide, and carbon monoxide concentrations and other important parameters of the interaction under various conditions were measured by cone calorimeter. The experiment illustrated that water mist would suppress the PVC fire by evaporation cooling, oxygen displacement and radiant heat attenuation. After the fire was extinguished and water mist was shut off, fire might reignite after a period of time. The reignition time depended on the total quantity of water mist.

Keywords

PVC fire / water mist / heat release rate / reignition

Cite this article

Download citation ▾
Huang Xin,Liu Jianghong,Zhang Yongfeng,Qin Jun. Study of Suppressing PVC Fire with Water Mist Using a Cone Calorimeter. Strategic Study of CAE, 2006, 8(12): 102‒106