Journal Home Online First Current Issue Archive For Authors Journal Information 中文版

Strategic Study of CAE >> 2004, Volume 6, Issue 7

Design of a Photoacoustic Gas Detection System for Fire Warning

State Key Laboratory of Fire Science, University of Science and Technology of China, Heifei 230027, China

Funding project:中国科学院知识创新方向性资助项目(KGCX2-308); 九七三国家重点基础研究发展规划资助项目(2001CB409608) Received: 2003-11-14 Available online: 2004-07-20

Next Previous

Abstract

The requirements and principles of using photoacoustic gas detection technique in fire detection area are discussed and an unusual photoacoustic gas detection system is presented. Common photoacoustic gas detection systems in laboratories are not suitable for fire warning because of their poor real-time performance and high wavelength qualification for the optical setup. Besides, they are too complex and expensive. These limitations can be solved with a different system design in which an enclosed photoacoustic cell filled with CO is used to achieve CO selection instead of optical filters or laser infrared source. Online CO measurement is realized in an exposed absorption path between the cell and the IR source. At first when there is no combustion gas in the absorption path, the CO cell absorbs the light radiation at 4.6 μm and gives an initial photoacoustic signal. Once combustion gases pass through, the contained CO composition can reduce the radiation that reaches the cell at 4.6 μm and accordingly attenuate the initial photoacoustic signal. Thus CO selection in the absorption path is achieved by enclosed CO itself in the cell, and the photoacoustic signal attenuation further indicates the CO concentration in the absorption path.

Figures

图1

图2

References

[ 1 ] 陈 涛, 袁宏永, 范维澄.火灾探测技术研究的展望[J].火灾科学, 2001, 10 (2) :108~112 link1

[ 2 ] RosePehrssonSL , ShafferRE , HartSJ, etal.Multi criteriafiredetectionsystemsusingaprobabilisticneuralnetwork[J ].SensorsandActuatorsB , 2000, 69 (3) :325~335

[ 3 ] GottukDT , PeatrossMJ.RobyRJ , etal.Advancedfiredetectionusingmulti signaturealarmalgorithms[J].FireSafetyJ, 2002, 37 (4) :381~394

[ 4 ] MilkeJA .Usingmultiplesensorsfordiscriminatingfiredetection[A ].FireSuppressionandDetectionResearchApplicationSymposium.ResearchandPractice:BridgingtheGap.Proceedings[C].OrlandoFL :NationalFireProtectionResearchFoundation, 1999.150~164

[ 5 ] HagenBChr, MilkeJA .Theuseofgaseousfiresignaturesasameantodetectfires[J].FireSafetyJ .2000, 34 (1) :55~67

[ 6 ] JacksonMA , RobinsI.Gassensingforfiredetection:measurementsofCO , CO2, H2, O2 andsmokedensityinEuropeanstandardfiretests[J].FireSafetyJ.1994, 22 (2) :181~205

[ 7 ] BlevinsLG .andPittsWM .Carbonmonoxidemeasurementusinganear infraredtunablediodelaser[R].Annualconferenceonfireresearch, bookof  abstracts[C].1998.NISTIR 6242.

[ 8 ] NebikerPW , PleischRE .Photoacoustic gasdetectionforfirewarning[J].FireSafetyJ.2001, 36 (2) :173~180

[ 9 ] 殷庆瑞, 王 通, 钱梦.光声光热技术及其应用[M].北京:科学出版社, 1991.146~150 link1

Related Research