Research Status and Future Development of Cooling Technologies for Green and Energy-Efficient Data Centers

1. College of Chemical Engineering, Beijing University of Chemical Technology, Beijing 100029, China;

2. Juhua Group Corporation, Quzhou 324004, Zhejiang, China;

3. School of Energy and Environment, Southeast University, Nanjing 210096, China

Funding project:National Key R&D Program of China (2021YFB3803200) Received: 2022-05-07 Revised: 2022-06-30 Available online: 2022-08-04

Next Previous

Abstract

Data centers are important infrastructure in China, with constantly increasing industry size, market revenues, and electricity consumption. The major cooling systems of data centers currently in operation in China are air-cooled, with a low energy utilization rate and great potentials for energy saving. Therefore, it is imperative to develop novel cooling technologies for green and energyefficient data centers. The cooling technology needs to solve two problems. First, as equipment heat production increases, the cooling capacity of the cooling system needs to be improved to match heat production and transfer rates. Second, to address the low energy efficiency problem, green and energy-efficient cooling technologies with industrial application prospects need to be developed. This study reviews the development status of data center cooling methods and categorizes cooling technologies into air conditioner cooling, fresh air cooling, indirect cooling, direct single-phase liquid cooling, and direct two-phase liquid cooling. We analyze the development trends of cooling technologies and suggest that green and high-efficient data centers should focus on the improvement in the efficiency of cooling systems, optimizations of hot and cold fluid channels, applications of new liquid cooling materials, and promotion of heat recovery systems. Furthermore, we propose suggestions for the stable and orderly development of the data center industry from the aspects of optimizing top-level design, developing key technologies, formulating scientific standards, improving industrial layout, and focusing on energy structure.

Figures

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

Fig. 7

Fig. 8

Fig. 9

Fig. 10

References

[ 1 ] China Academy of Information and Communications Technology (CAICT). Data center white paper (2022) [R]. Beijing: China Academy of Information and Communications Technology (CAICT), 2022. Chinese.

[ 2 ] Lu T, Lyu X S, Remes M, et al. Investigation of air management and energy performance in a data center in Finland: Case study [J]. Energy & Buildings, 2011, 43(12): 3360‒3372.

[ 3 ] Ji X L. Ecological and green development: The installed capacity of power generation is getting cleaner and the data center is getting more and more energy-efficient [N/OL]. China Economic Herald, (2021-07-29) [2022-05-02]. Chinese. link1

[ 4 ] Bao K L, Wang X H, Fang Y B, et al. Effects of the surfactant solution on the performance of the pulsating heat pipe [J]. Applied Thermal Engineering, 2020, 178: 115678.

[ 5 ] CCID. White Paper on the Development of China Liquid-Cooled Data Centers [R/OL]. Beijing: CCID Consulting Co., Ltd., (202012) [2022-04-15]. Chinese. link1

[ 6 ] Zhu Y Z. The application and development of data center refrigeration technology [J]. Standardization of Engineering Construction, 2015 (8): 62‒66. Chinese.

[ 7 ] Jing C G, Li N, Song X W. Effect of different power density racks on data center [J]. Telecom Power Technologies, 2019, 36(10): 4. Chinese.

[ 8 ] CHENG B, WANG T, WU H, et al. The strategy and application of energy saving and emission reduction in China telecom data center [J]. Energy Conservation, 2012, 31(1): 4-8. Chinese.

[ 9 ] Garimella S V, Yeh L T, Persoons T. Thermal management challenges in telecommunication systems and data centers [J]. IEEE Transactions on Components, Packaging and Manufacturing Technology, 2012, 2(8): 1307‒1316.

[10] Liu Y, Guan R B, Jing M, et al. Research of data center fresh air ventilation cooling system [J]. Lecture Notes in Electrical Engineering, 2014, 262: 299‒306.

[11] Geng H Y. Data center handbook [M]. Hoboken: John Wiley & Sons, 2014.

[12] Tuma P E. The merits of open bath immersion cooling of datacom equipment [C]. Santa Clara: Proceedings of the 2010 26th Annual IEEE Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2010.

[13] ELLSWORTH M J. Flow network analysis of the IBM Power 775 supercomputer Water Cooling System [C]. Orlando: Proceedings of the 2014 IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2014.

[14] Xiao X W. On heat recovery in data centers cooled by cold plate direct contact liquid cooling system [J]. Building Energy Efficiency, 2020, 48(2): 69‒73. Chinese.

[15] Xie L N, Guo L. Discussion on liquid cooling technology and development [J]. Information and Communications Technology and Policy, 2019, 296(2): 29‒32. Chinese.

[16] Han X H, Wang X H, Zheng H C, et al. Review of the development of pulsating heat pipe for heat dissipation [J]. Renewable and Sustainable Energy Reviews, 2016, 59: 692‒709.

[17] Kheirabadi A C, Groulx D. Cooling of server electronics: A design review of existing technology [J]. Applied Thermal Engineering, 2016, 105: 622‒638.

[18] Mcglen R J, Jachuck R, Lin S. Integrated thermal management techniques for high power electronic devices [J]. Applied Thermal Engineering, 2004, 24(8‒9): 1143‒1156.

[19] Zheng S M. Application of heat pipe technology in data center cooling system [J]. Journal of Green Science and Technology, 2019 (24): 187‒188. Chinese.

[20] Tian H, Li Z. Distributed cooling scheme of data center based on loop heat pipe technology and its application [J]. World Telecommunications, 2011 (10): 48‒52. Chinese.

[21] EL-GENK M S. Immersion cooling nucleate boiling of high power computer chips [J]. Energy Conversion & Management, 2012, 53(1): 205‒218.

[22] Zhong Y F, Guo R, Zhang J, et al. Long-term reliability evaluation of single-phase immersion liquid-cooling server based on electronic fluoride [J]. China Telecommunications Trade, 2021 (S1): 55‒60. Chinese.

[23] Park J E, Thome J R. Critical heat flux in multi-microchannel copper elements with low pressure refrigerants [J]. International Journal of Heat & Mass Transfer, 2010, 53(1‒3): 110‒122.

[24] Kim J. Spray cooling heat transfer: The state of the art [J]. International Journal of Heat & Fluid Flow, 2007, 28(4): 753‒767.

[25] Guo D, Wei J J, Zhang Y H. Enhanced flow boiling heat transfer with jet impingement on micro-pin-finned surfaces [J]. Applied Thermal Engineering, 2011, 31(11‒12): 2042‒2051.

[26] Johnston A, Stone D, Cader T. SprayCool command post platform for harsh military environments [C]. San Jose: 2008 Twentyfourth Annual IEEE Semiconductor Thermal Measurement and Management Symposium, 2008.

[27] Qiu L, Dubey S, Choo F H, et al. Recent developments of jet impingement nucleate boiling [J]. International Journal of Heat and Mass Transfer, 2015, 89: 42‒58.

[28] Liu S Y, Ruan L, Kang Y H. Experimental investigation and numerical analysis of atomization characteristics at the spray cooling axis [J]. Science Technology and Engineering, 2018 (2): 225‒229. Chinese.

[29] Yang J, Chow L C, Paris M R. Nucleate boiling heat transfer in spray cooling [J]. Journal Heat Transfer, 1996, 118(3): 668‒671.

[30] Silk E A, Golliher E L, Selvam R P. Spray cooling heat transfer: Technology overview and assessment of future challenges for micro-gravity application [J]. Energy Conversion & Management, 2008, 49(3): 453‒468.

[31] Rasmussen N. An improved architecture for high-efficiency, highdensity data centers [J]. Green Grid White Paper, 2008, 126: 1‒25.

[32] Joshi Y, Kumar P. Energy efficient thermal management of data centers [M]. Boston: Springer, 2012.

[33] Takahashi M, Uekusa T, Kishita M, et al. Aisle-capping method for airflow design in data centers [C]. San Diego: proceedings of the Telecommunications Energy Conference, 2008.

[34] Bash C E, Patel C D, Sharma R K. Efficient thermal management of data centers—Immediate and long-term research needs [J]. Hvac & R Research, 2003, 9(2): 137‒152.

[35] Ayou D S, Bruno J C, Saravanan R, et al. An overview of combined absorption power and cooling cycles [J]. Renewable & Sustainable Energy Reviews, 2013, 21: 728‒748.

[36] Brunschwiler T, Smith B, Ruetsche E, et al. Toward zeroemission data centers through direct reuse of thermal energy [J]. IBM Journal of Research and Development, 2009, 53(3):1‒13.

[37] Ebrahimi K, Jones G F, Fleischer A S. A review of data center cooling technology, operating conditions and the corresponding low-grade waste heat recovery opportunities [J]. Renewable & Sustainable Energy Reviews, 2014, 31(2): 622‒638.

[38] Sun C F, Zhang L. Development Trend and Application of Data Center Server Technology [J]. Communications World, 2021 (10): 37‒38. Chinese.

Related Research